Intrinsically Safe Flashing Alarm Beacons
Provide Alarm Notification in Hazardous Locations & Extreme Environments
Photo of E2S Model IS-MB1 intrinsically safe flashing LED alarm beacon IS-MB1 I.S. LED Flashing Beacon
  • Intrinsically safe
  • FM, ATEX & IECEx certification
  • Takes 16-28 VDC from suitable safety barrier
  • Six high-intensity LEDs
  • Prismatic lens in choice of five colors
  • Double flash at once or twice per second
  • IP65 ABS flame retardant housing
  • End-of-line resistor certification
  • Economical solution for industrial fire & gas detection systems
Mark of certification to ATEX Directive Mark of certification to IECEx standard Mark of Factory Mutual approval
Value priced at $244.00
IS-MB1 Specifications
Certification Factory Mutual: Cl I, Div 1, Grp A-D; Class I, Zone 0, AEx ia IIC T4
ATEX & IECEx: II 1G EEx ia IIC T4 (-40°C<=Ta<=+60°C)
Operating Voltage 16-28VDC via Zener or galvanically isolated safety barrier
Current Draw 25mA typical when powered from 24VDC via a safety barrier; beacon has internal current limiting and reverse current protection
Light Source Six high intensity LEDs with prismatic lens to optimize LED visibility
Light Output Double flash in two configurable modes: 1Hz / 2Hz
Lens Colors Red, orange/amber, green, blue, clear
Dimensions 3.35 h x 3.74 dia* inches / 85 h x 95 dia* mm
*includes lens fastener protrusion
Operating Temperature -40 to +140°F / -40 to +60°C
Environmental Protection IP65; Housing material: ABS flame retardant; Lens: polycarbonate.
Relative humidity: 90% max. @ 120
°F / 50°C
Cable Entry 2x M20 knockouts
Other End-of-line resistor certified for fire & gas alarm systems
Photo of E2S Model IS-MC1 combined intrinsically safe alarm sounder and flashing LED alarm beacon
IS-MC1 I.S. Combination LED Flashing Beacon & Alarm Sounder
  • Intrinsically safe
  • FM, ATEX & IECEx certification
  • Takes 16-28 VDC from suitable safety barrier
  • Six high-intensity LEDs
  • Prismatic lens in choice of five colors
  • Double flash at once or twice per second
  • Loud 100 dB(A) audible output
  • Choice of 49 alarm tone combinations, 3 stages
  • IP65 ABS flame retardant housing
  • End-of-line resistor certification
  • Economical solution provides visible and audible alarm in one compact unit
  • Perfect for industrial fire & gas alarm systems
Mark of certification to ATEX Directive Mark of certification to IECEx standard Mark of Factory Mutual approval
Value priced at $385.00
IS-MC1 Specifications
Certification Factory Mutual: Cl I, Div 1, Grp A-D; Class I, Zone 0, AEx ia IIC T4
ATEX & IECEx: II 1G EEx ia IIC T4 (-40°C<=Ta<=+60°C)
Operating Voltage 16-28VDC via Zener or galvanically isolated safety barrier
Current Draw 25mA each typical for beacon and sounder powered separately from 24VDC via safety barriers, 30mA total typical when beacon and sounder are powered from a common barrier; unit has internal current limiting and reverse current protection
Light Source Six high intensity LEDs with prismatic lens to optimize LED visibility
Light Output Double flash in two configurable modes: 1Hz / 2Hz
Lens Colors Red, orange/amber, green, blue, clear
Alarm Sound Output 100 dB(A) @ 1 m; effective range up to 130' / 40 m @ 1kHZ
Alarm Sound Modes 49 configurable tone combinations, 3 stages (PFEER/UKOOA compliant)
Dimensions 4.60" h x 3.74" dia* / 116 h x 95 dia* mm
*includes lens fastener protrusion
Operating Temperature -40 to +140°F / -40 to +60°C
Environmental Protection IP65; Housing material: ABS flame retardant; Lens: polycarbonate.
Relative humidity: 90% max. @ 120
°F / 50°C
Cable Entry 2x M20 knockouts
Other End-of-line resistor certified for fire & gas alarm systems
Photo of Beka Model BA386 intrinsically safe flashing LED alarm beacon BA386 I.S. LED Flashing Beacon
  • Intrinsically safe
  • FM and ATEX certification
  • Choice of five colors
  • Two double flashes per second
  • IP56 environmental rating
  • Compatible with a wide range of barriers
  • Can power BR385 sounder with same safety barrier
Mark of certification to ATEX Directive Mark of Factory Mutual approval
The BA386 provides a bright flashing warning signal in a plant or processing area where ambient noise levels may drown out an audible alarm. It is significantly less expensive than traditional Xenon devices, yet has a similar light output and flashes more rapidly – making it more immediately noticable. Available in five colors to enable multi-stage alarm level protocols. Factory Mutual and ATEX intrinsic safety certification enable it to be used in virtually any classified hazardous location. Ask us about suitable intrinsic safety barriers.
Photo of combined Beka BA386 intrinsically safe alarm beacon and BR385 intrinsically safe alarm sounder for use in hazardous classified locations
Can be used in conjunction with a BR385 alarm sounder using a single 28V 93mA 0.66W Zener barrier or galvanic isolator. The BA386 beacon includes terminals to power the sounder, and for an external push button to silence the sounder. The silence time is adjustable from 1 to 30 minutes. We can even supply a kit to combine the two units.
Photo of RTK Model DA135 intrinsically safe flashing LED alarm beacon DA135 I.S. LED Flashing Beacons
  • Intrinsically safe
  • ATEX II 1 G EEx ia IIC T6
  • Choice of five colors
  • Single, dual, or triple flash modes
  • Dual color option
  • IP65 environmental rating
  • May be combined with sounder and pushbutton
  • Isolated control connections
  • Compatible with a wide range of barriers
  • Pipe or wall mounting
Mark of certification to ATEX Directive
DA135 beacons offer multiple alarm modes to provide visual warnings in a variety of situations. A choice of five bright colors – including blue and white - plus single, dual and triple flash cycles. There's even a dual color option to warn operators of a relative change in status. Protective lenses appear clear until the LEDs are illuminated. Each beacon may be connected to a sounder and acknowledge/reset pushbutton to create a local alarm station. The electronics are totally encapsulated, and wiring connections are made in a separate terminal chamber. All control connections are fully isolated to simplify circuit design. Ask us about suitable intrinsic safety barriers and isolators.
Photo of RTK Model LN870 intrinsically safe stack light and light tower
LN870 I.S. LED Stack Lights
  • Intrinsically safe
  • ATEX II 2 G EEx ia IIC T4
  • Available in five bright colors
  • Reliable LED illumination
  • 10+ year continuous life expectancy
  • Low current consumption
  • Built-in vibration shock absorber
  • Surface or pole mounting
  • Compatible with a wide range of barriers
  • No explosion-proof housing required
Mark of certification to ATEX Directive
Multi-color signalling comes to hazardous locations in the form of the LN870 light tower. Bright LEDS enable this design to be certified as intrinsically safe when used with the appropriate safety barriers — ask us about economical multi-channel isolating intrinsic safety barriers. Up to five lamp segments can be stacked and there are five different colors to choose from.
You may also be interested in these related products: