Exloc Instruments: your one-stop-shop for instruments and electrical equipment for use in hazardous classified locations.
Saving you time & money solving challenging problems!
Operator Stations & HMIs for Hazardous Locations
Serial Data Terminals
Intrinsically safe
High contrast display with backlight
Display up to 8 variables
Operator push buttons & switch outputs
Field & panel mounting models
BEKA, Modbus, and legacy protocols
Text may be written anywhere on the screen in five different font sizes, together with lines, boxes, bargraphs and simple bitmap graphics. Choose from nine screens, or customize. Learn more....
Challenger 15i & 18i
Intrinsically Safe PC Terminals
16 million color TFT display.
15" XGA (1024 x 768 pixels).
18" SXGA (1280 x 1024 pixels).
105 key QWERTY keyboard.
Optional pointing devices.
IP65 ingress protection.
Stand alone stations or modular installation in existing panels.
ATEX, UL and C-UL approvals.
No purging system required.
Challenger intrinsically safe PC terminals permit plant operators full remote access to software running on a conventional IBM-compatible PC or UNIX machine. Various combinations of display, keyboard and pointing device may be connected to a PC located back in an unclassified area via a data transmission card which also incorporates the intrinsic safety interface. The physical data connection is made with CAT6/7 four-pair STP cable. Transmission distances up to 1,600 feet (500 meters) are possible, and up to four terminals and associated data transmission cards can be supported by a single PC.
Compared with previously used protection techniques involving purged or explosion proof enclosures, the Challenger system enables easy installation of remote terminals. Because the associated PC remains in an unclassified plant area (usually a control room) it may be upgraded or replaced at any time without affecting the safety or set-up of the remote terminal.
Challenger terminals are available as a fully assembled station for floor, wall, or ceiling mount, or as individual modules to install in your existing panel or custom enclosure. Off-the-shelf enclosures and mounting accessories are manufactured from stainless steel and designed to meet the rugged performance requirements of industrial applications.
New modules are always under development ask about touch-screen displays, card readers, barcode scanning, fingerprint recognition, etc.
Specifications
Flat Panel Displays
15.1", TFT with 16 million colors, XGA, 1024 x 768 pixels.
FMO15I
18.1", TFT with 16 million colors, SXGA, 1280 x 1024 pixels.
FMO18i
Keyboard
105-key QWERTY layout, IBM compatible, pushbuttons under protective membrane.
U.S. English
KBiQY
German
KBiQZ
French
KBiAY
Pointing Devices
Trackball with two keys.
TBi
Finger mouse with two keys, speed & direction control.
Mi
Terminal Enclosure
Field desk enclosure, two-part, rear opening door on display section, keyboard section inclined at 30 deg. Hygienic stainless steel polished to 240 grit. IP65.
15" display
FHP15
18" display
FHP18
Terminal Standpipe
Floor or ceiling, with flange, two cable glands. Hygienic stainless steel. Standard length: 1260mm. Diameter: 60.3mm
STF
Terminal Wall Elbow
90 deg. elbow for wall mounting, with flange, two cable glands. Hygienic stainless steel. Standard length: 300x150mm. Diameter: 60.3mm.
EBF
Terminal Coupling
Required to couple the FHP enclosure to either the standpipe STF or elbow EBF. Enables enclosure to be rotated 300 deg.
for service. Hygienic stainless steel.
MB
Power Supply (terminal)
Power supply module typically mounted in back of terminal enclosure, 24VDC, 2.5A
15" display
PSU14i-6
18" display
PSU14i-8
Interface Card
Accepts VGA, PS2 keyboard and mouse connections from PC in non-hazardous location; provides intrinsically safe data connections for terminal in hazardous location.
TCV2i
Power Supply (TCV2i)
Power supply card for powering up to four TCV2i modules,
110 VAC
PSU2
Rack Mounting (TCV2i)
19" rack assembly, pre-wired, can house up to four TCV2i transmission cards and one PSU2 power supply card.
R842
Desk Housing (TCV2i)
Desk top housing, pre-wired, can house up to two TCV2I transmission cards and one PSU2 power supply card.
R422
Options
Key Switch, mounted on terminal Enclosure FHP. Locks keyboard and trackball/mouse on terminal.
SW1
Key Switch, integrated into Rack R842 or Desk Top Housing R422. Locks keyboard and trackball/mouse on terminal and/or the PC.
SW2
Ambient Temperature
-10 to +50°C (+14 to +122°F).
Environmental
Terminal modules (only) rated IP65 from front. Stainless steel polished to 240 grit.
Hazardous Location Approvals
UL/C-UL: Class I, Zone 1, Ex ib IIC T4.
ATEX: II 2G EEx ib IIC T4.
CHALLENGER for non-hazardous locations ask about the general purpose versions which retain all of the rugged design features and flexibilty of the products described here. Make Challenger the industrial terminal of choice throughout your plant.
EXPLORER 15i & 18i Em PC
for use in Hazardous Areas
Ex Zone 1/2/22 certification
Operator terminal and PC combined
Intel® 1.6 GHz Pentium® processor
1GB RAM, 60GB hard drive
Panel mounting
Modular configuration
USB, Serial, and Ethernet connectivity
Available Models
Hazardous Locations
General Purpose Locations
EXPLORER 15i Em PC Intrinsically safe
15" TFT display XGA (1024 x 768)
EXPLORER 18i Em PC Intrinsically safe
19" TFT display SXGA (1280 x 1024)
EXPLORER 15 Em PC Industrial grade
15" TFT display XGA (1024 x 768)
EXPLORER 18 Em PC Industrial grade
19" TFT display SXGA (1280 x 1024)
Common Specification
CPU
Intel® Pentium® Processor 1.6 GHz
RAM
1024 MB
Video controller
Intel® Extreme Graphics 2 Controller
Display
TFT display, 16.7 million colors, Full Screen Mode automatically
Contrast
250:1 (typical)
Backlighting
Longlife CCFL, 50,000 hours (typical)
Brightness
250 / 650 cd/m2
Viewing angle
160°
Ethernet
EEx e 10/100 Mbit
USB ports
3 x USB 2.0 EEx i, 1 x USB 2.0 EEx e
Serial interface ports
1 x RS232 EEx i, 1 x RS232 EEx e or RS422 EEx e or RS485 Ex e
Power supply
110-240VAC (wide range), 50-60 Hz, 75W
Operating temperature range
-10°C to +60°C (typical),
-30°C to +60°C (special order)
Options
High Brightness Display
Touch Screen
Extended Operating Temperature Range
Emergency Stop Button
USB Memory Stick
Bluetooth Data Transmission up to 100 meters