Alarm Sounders for Hazardous Locations
IS-MA1 I.S. Alarm Sounder
Intrinsically safe
FM, ATEX & IECEx certification
Takes 16-28 VDC from suitable safety barrier
Loud 100 dB(A) audible output
Choice of 49 alarm tone combinations, 3 stages
Effective range of 130 feet / 40 meters at 1 kHz
IP65 ABS flame retardant housing
End-of-line resistor certification
Economical solution for industrial fire & gas detection systems
Specification
Certification
Factory Mutual: Cl I, Div 1, Grp A-D; Class I, Zone 0, AEx ia IIC T4
ATEX & IECEx: II 1G EEx ia IIC T4 (-40°C<=Ta<=+60°C)
Operating Voltage
16-28VDC via Zener or galvanically isolated safety barrier
Current Draw
25mA typical when powered from 24VDC via a safety barrier; sounder has internal current limiting and reverse current protection
Alarm Sound Output
100 dB(A) @ 1 m; effective range up to 130' / 40 m @ 1kHZ
Alarm Sound Modes
49 configurable tone combinations, 3 stages (PFEER/UKOOA compliant)
Dimensions
4.60" h x 3.74" dia* / 116 h x 95 dia* mm
*includes lens fastener protrusion
End-of-line resistor certified for fire & gas alarm systems
IS-MC1 I.S. Combination LED Flashing Beacon & Alarm Sounder
Intrinsically safe
FM, ATEX & IECEx certification
Takes 16-28 VDC from suitable safety barrier
Six high-intensity LEDs
Prismatic lens in choice of five colors
Double flash at once or twice per second
Loud 100 dB(A) audible output
Choice of 49 alarm tone combinations, 3 stages
IP65 ABS flame retardant housing
End-of-line resistor certification
Economical solution provides visible and audible alarm in one compact unit
Perfect for industrial fire & gas alarm systems
Specification
Certification
Factory Mutual: Cl I, Div 1, Grp A-D; Class I, Zone 0, AEx ia IIC T4
ATEX & IECEx: II 1G EEx ia IIC T4 (-40°C<=Ta<=+60°C)
Operating Voltage
16-28VDC via Zener or galvanically isolated safety barrier
Current Draw
25mA each typical for beacon and sounder powered separately from 24VDC via safety barriers, 30mA total typical when beacon and sounder are powered from a common barrier; unit has internal current limiting and reverse current protection
Light Source
Six high intensity LEDs with prismatic lens to optimize LED visibility
Light Output
Double flash in two configurable modes: 1Hz / 2Hz
Lens Colors
Red, orange/amber, green, blue, clear
Alarm Sound Output
100 dB(A) @ 1 m; effective range up to 130' / 40 m @ 1kHZ
Alarm Sound Modes
49 configurable tone combinations, 3 stages (PFEER/UKOOA compliant)
Dimensions
4.60" h x 3.74" dia* / 116 h x 95 dia* mm
*includes lens fastener protrusion
End-of-line resistor certified for fire & gas alarm systems
BR385 I.S. Alarm Sounder
Intrinsically safe
Up to 103 dB(A) output
49 first stage, 21 second stage,
and 9 third stage alarm tones
PFEER compliant
Volume control
IP66 environmental rating
Input overload protection
With forty-nine alarm tones to choose from these intrinsically safe sounders allow you to pick sounds which will penetrate the ambient background noise in your plant. Second and third stage tones are easily triggered by secondary control circuits. Tones are selected by DIP switches, and there's also a volume control. A crystal controlled oscillator accurately defines the frequency and repetition rate of each alarm signal. This insures that multiple sounders set to the same tone(s) remain synchronized throughout your plant. Ask us about suitable intrinsic safety barriers.
BExS110D Alarm Sounder
Flameproof.
ATEX EEX d IIC T4 certification.
Up to 113 dB(A) output.
32 different tones.
Second & third stage outputs.
PFEER compliant.
IP67 environmental rating.
12, 24, or 48VDC; 115 or 230VAC .
Mounting bracket included.
Where an EEx d installation is acceptable the BExS110D sounder will provide an extremely effective audible alarm. There's a choice of thirty two user selectable tones, plus provision to enable second and third stage sounds by secondary control circuits. In the case of 24VDC powered units an end-of-line resistor or diode may be installed inside the beacon enclosure for line monitoring purposes. An alternative stainless steel pipe mounting kit is available.