Exloc Instruments Logo
Search
Close this search box.

GMI D5040D Intrinsically Safe Isolator SIL 3 Digital Output Driver, NE Loads, Loop Powered

GET A QUOTE – For business orders requiring a written quote or for volume pricing please request a quote.

The dual channel Loop Powered Digital Output Isolators D5040D is suitable for driving solenoid valves, visual or audible alarms to alert a plant operator, or other process control devices in Hazardous Area from driving signals in Safe Area. It can also be used as controllable supply to power measuring or process control equipment.

Its use is allowed in applications requiring up to SIL 3 level (according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries. The Safety PLC or DCS driving signals control the field devices through D5040D, which provide isolation.
For each channel two basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market. The selection among the two output characteristics is obtained by connecting the field device to a different couple of terminal blocks.
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area or in Class I, Division 2 or Zone 2.

 

We are an authorized GMI distributor shipping to locations in North America.

$351.00

Connect with Hazardous Area Expert

Questions
or Volume Pricing?

Connect with Hazardous Area Expert:
281-978-2040 | Chat with Us
Get Quote

Description

  • SIL 3 according to IEC 61508:2010 Ed. 2 for lifetime = 20 yrs
  • PFDavg (1 year) 0.00 E+00, SFF 100 %
  • Output to Zone 0 (Zone 20), installation in Zone 2
  • Loop powered for NE loads
  • Output short circuit proof and current limited
  • Two port isolation, Input/Output
  • EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety systems
  • Simplified installation using standard DIN-Rail and plug-in terminal blocks, or customized Termination Boards
  • 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier
  • Operating temperature range up to: -40 to +70 °C / -40 to +158°F
  • Certified for Offshore and Marine applications

Approvals

  • UL-Underwriters Laboratory
  • ATEX
  • IECEx
  • TUV Certificate Summary

 

Resources

HAZARDOUS AREA INSTRUMENTS
BACKED WITH INDUSTRY LEADING SERVICE AND SUPPORT

Download Product and Service Catalogs

Fill out your contact details and we will forward you to download our product brochures. 

HAZARDOUS AREA INSTRUMENTS
BACKED WITH INDUSTRY LEADING SERVICE AND SUPPORT