Description
GET A QUOTE – Not available for purchase online. Please click the link to request a quote or call 281-545-3968.
Pageant is an intrinsically safe combined PLC and local operator panel with provision for plug-in input and output modules. It may be safely installed in Zones 0, 1, 2, 20, 21 or 22 hazardous areas and can economically monitor and control hazardous area equipment such as mud pumps, pharmaceutical coating machines and flammable liquor stills. Pageant can operate alone or as part of an integrated control system.
Designed with the help of users Pageant features a seven inch back-lit operator display which is readable in all lighting conditions. Up to seven plug-in analogue or digital input and output interface modules can be accommodated plus a CPU module with an IEC 61131 compliant CODESYS® PLC and optional external communications. Operator inputs are made via eight touch buttons each with a programmable tricolor annunciator.




Technical Data
Model | BA3101 |
---|---|
Details on Datasheet | |
Mounting | Panel 248.5 x 184mm |
Protection | Front IP66, rear IP20 |
Resources
- Pageant Product Summary
- Pageant Explained
- Datasheet
- IECEx Certificate
- ATEX Certificate
- UKEX Certificate
- Instruction Manual
- Pageant Operator Panel System Manual
- Pageant Codesys Quick Start Guide
- CODESYS Control for Pageant Package
- Declaration of Conformity (EU)
- Declaration of Conformity (UK)
- CAD Files
Certifications




International IECEx |
Gas - Ex ia IIC T4 Ga -40°C ≤ Ta ≤ +65°C Dust - Ex ia IIIC T135ºC Da -40°C ≤ Ta ≤ +65°C |
Europe ATEX |
Gas - Group II Category 1G Ex ia IIC T4 Ga -40°C ≤ Ta ≤ +65°C Dust - Group II Category 1D Ex ia IIIC T135ºC Da -40°C ≤ Ta ≤ +65°C |
UK UKEX |
Gas - Group II Category 1G Ex ia IIC T4 Ga -40°C ≤ Ta ≤ +65°C Dust - Group II Category 1D Ex ia IIIC T135ºC Da -40°C ≤ Ta ≤ +65°C |