EXCEN NRG 3K ATEX/IECEx Certified UPS System for Hazardous Areas (Zone 1/2/21/22)


Highlights

Highlights

Description

The EXCEN NRG 3K is an ATEX and IECEx certified UPS system providing reliable backup power for hazardous areas in Zone 1, Zone 2, Zone 21, and Zone 22. In its standard configuration it delivers up to 6 kVA (see the thermal derating table) with a fast transfer time of 15 ms or less, making it well suited for instrumentation, control, and auxiliary systems. The system features IP66 protection, a modular design on a robust frame, and a glass inspection window for viewing system status and alarms. It is supplied ready to install with an ATEX & IECEx certified AGM, GEL, or NiCd battery in a stainless steel enclosure and a dedicated battery breaker. Custom power and input/output ratings are available on request.

Ex IECEx

Technical Data

Electrical
Power ratingUp to 6 kVA (standard configuration, see thermal derating)
Input voltage and frequency150 to 265 Vac / 50 to 140 Vac
45 to 65 Hz
Output voltagePure sine wave 230 Vac (±2%) / 120 Vac
Output frequency50 Hz ±0.05% (crystal controlled)
45 to 65 Hz programmable
Transfer time≤ 15 ms
Battery
BatteryATEX & IECEx certified, in stainless steel enclosure
Battery technologyAGM, GEL, or NiCd
Battery protectionDedicated battery breaker between UPS and battery
Construction
Protection ratingIP66
DesignModular, mounted on a robust frame
Status displayGlass inspection window for system status and alarms
Dimensions (example configuration with distribution and bypass options)Approx. 56.9 x 54.8 x 19.7 in (1445 x 1393 x 501 mm)
Optional on requestCopper free aluminum or SS316L Exd enclosures
Protective coatings for corrosion resistance
Power distribution
System bypass
Thermal Derating: Maximum Output Power vs. Ambient Temperature
500 VAUp to 55 °C (131 °F)
1000 VAUp to 50 °C (122 °F)
1500 VAUp to 48 °C (118 °F)
2000 VAUp to 45 °C (113 °F)
2500 VAUp to 42 °C (108 °F)
3000 VAUp to 40 °C (104 °F)
5000 VAUp to 35 °C (95 °F)
6000 VAUp to 30 °C (86 °F)
Estimated Battery Backup Time (48 VDC, 205 Ah battery bank at 25 °C / 77 °F)
500 VA15 h 00 min
1000 VA7 h 30 min
1500 VA4 h 30 min
2000 VA3 h 15 min
2500 VA2 h 30 min
3000 VA2 h 00 min
5000 VA1 h 00 min
6000 VA0 h 45 min
Actual backup time may vary depending on inverter cut-off voltage threshold, battery age, temperature, and real efficiency.

Approvals

Ex trans small logo IECEx Logo

ATEX (Europe)
Zone 1, Zone 2, Zone 21, Zone 22

IECEx (International)
Zone 1, Zone 2, Zone 21, Zone 22

Includes

  • NRG 3K UPS System
  • ATEX & IECEx Certified Battery in Stainless Steel Enclosure
  • Dedicated Battery Breaker

Power distribution and system bypass are available as options.