- Description
- Technical Data
- Resources
- Approvals
Description
GET A QUOTE – Not available for purchase online. Please click the link to request a quote or call 281-688-9468.
Compact Remote IO modules for Ex Zone 1/21 or Zone 2/22. with Profinet or Modbus TCP/IP. The modules include busnode, isolating amplifier and 32 intrinsically safe analog and digital IO channels on smallest space.
BEx1 module can be installed in Zone 1/21 with certified Ex e enclosure and connects to sensors and actuators from Zone 0/20.
BEx2 module can be installed in Zone 2/22, in a suitable housing according to EN 60079-7:2018 with a protection degree of at least IP 54 and connects to sensors and actuators from Zone 0/20.


Technical Data
Operating voltage UA/US DC 18 ... 30V
Power supply module and sensors IS DC 450 mA
Power supply actuators IA DC 300 mA
Power loss max. 15W
Reverse polarity protection Yes
Range of the service temperature after installation inside
Additional housing -40°C ... +70°C
Storage temperature -40°C ... +80°C
Degree of protection (EN 60529) IP 20
Addressing Profinet via DCP
Addressing Modbus TCP / IP DHCP or fix
Transfer rate 10/100 Mbps
Delay at signal change <10ms
• 16xDI Namur / 16xDO
• 32x DI Namur
• 8xDI Namur / 8xDO / 8xAI / 8xAO
• 8xDI Namur / 16xDO / 8xAI
• 8xDI Namur / 8xDO / 8xSwitch Mode
Dimensions (LxWxH) 214 x 132 x 65 mm
Installation position any position
Weight approx. 2700 g
Housing material Aluminum (electroplated)
Resources
- BEx1 IO Box
- BEx Remote IO Modules Data Sheet
- BEx Manual
- BEx1 EU Declaration of Conformity
- BEx2 EU Declaration of Conformity
- BEx1 EU-Type Examination Certificate EPS 19 ATEX 1 219 X
- BEx2 Certificate of Conformity EPS 19 ATEX 1 248 X
- BEx1 IECEx Certificate of Conformity IECEx EPS 19.0093X
- BEx2 IECEx Certificate of Conformity IECEx EPS 19.0111X
- Zertifikat PNO Profinet
Approvals


BEx1 Explosion Protection
EPS 19 ATEX 1 219 X<
II 2(1) G Ex eb mb [ia Ga] IIC T4 Gb
II (1) D [Ex ia Da] IIIC
IECEx EPS 19.0093X
Ex eb mb [ia Ga] IIC T4 Gb
[Ex ia Da] IIIC
BEx2 Explosion Protection
EPS 19 ATEX 1 248 X
II 3(1) G Ex ec mc [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] IIIC
IECEx EPS 19. 0111X
Ex ec mc [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC