- Description
- Technical Data
- Resources
Description
GET A QUOTE – Not available for purchase online. Please click the link to request a quote or call 281-336-9070.
These loop powered increased safety Ex eb certified indicators are a lower cost alternative to flameproof Ex d indicators, featuring large high contrast displays with a very wide viewing angle. They may be connected into any 4/20mA Zone 1 or 2 loop with any type of explosion protection apart from intrinsic safety.
No additional charge is made for factory calibration or for scale and tag marking, however the indicators can easily be recalibrated on-site.
Technical Data
| BA324SG | |
|---|---|
| Mounting & Enclosure |
Field 122 x 120 |
| Protection | IP66 |
| Display |
5 digits 29mm high + bargraph |
| Certification | |
|
International IECEx |
Gas - Ex eb ib mb IIC T5 Gb
Increased safety Ex eb Dust - Ex ib mb tb T80°C Db Protection by enclosure Ex tb -40°C ≤ Ta ≤ 60°C Cert. No. IECEx ITS 19.0018X |
|
Europe ATEX |
Gas - II 2G Ex eb ib mb IIC T5 Gb
Increased safety Ex eb Dust - II 2D Ex ib mb tb T80°C Db Protection by enclosure Ex tb -40°C ≤ Ta ≤ 60°C Cert. No. ITS19ATEX304891X |
|
UK UKEX |
Gas - II 2G Ex eb ib mb IIC T5 Gb
Increased safety Ex eb Dust - II 2D Ex ib mb tb T80°C Db Protection by enclosure Ex tb -40°C ≤ Ta ≤ 60°C Cert. No. ITS21UKEX0100X |
|
USA ETL & Canada cETL |
Class I Zone 1 AEx eb ib mb IIC T5 Gb (USA) Ex eb ib mb IIC T5 Gb (Canada) -40°C ≤ Ta ≤ +60°C |
| Optional | |
| Backlight | Yes |
| Escutcheon scale and tag labelling (no charge) | Yes |
| Etched stainless steel legend plate | Yes |